INSPECTION
PROCEDURE
1. INSPECT SHIFT SOLENOID VALVE SR
(a) Measure the resistance according to the value(s) in the table below.
Standard Resistance:
Tester Connection |
Condition |
Specified Condition |
---|---|---|
Shift solenoid valve SR connector terminal - Shift solenoid valve SR body |
20°C (68°F) |
11 to 15 Ω |
*a |
Component without harness connected (Shift Solenoid Valve SR) |
(b) Apply 12 V battery voltage to the shift solenoid valve and check that the valve moves and makes an operating noise.
OK:
Measurement Condition |
Specified Condition |
---|---|
|
Valve moves and makes an operating noise |
If the result is not as specified, replace the solenoid valve.
2. INSPECT SHIFT SOLENOID VALVE SL1 AND SL2
(a) Measure the resistance according to the value(s) in the table below.
Standard Resistance:
Tester Connection |
Condition |
Specified Condition |
---|---|---|
1 - 2 |
20°C (68°F) |
5.0 to 5.6 Ω |
*a |
Component without harness connected (Shift Solenoid Valve) |
(b) Apply 12 V battery voltage to the shift solenoid valve and check that the valve moves and makes an operating noise.
OK:
Measurement Condition |
Specified Condition |
---|---|
|
Valve moves and makes an operating noise |
If the result is not as specified, replace the solenoid valve.
3. INSPECT SHIFT SOLENOID VALVE SLT AND SLU
(a) Measure the resistance according to the value(s) in the table below.
Standard Resistance:
Tester Connection |
Condition |
Specified Condition |
---|---|---|
1 -2 |
20°C (68°F) |
5.0 to 5.6 Ω |
*a |
Component without harness connected (Shift Solenoid Valve) |
(b) Apply 12 V battery voltage to the shift solenoid valve and check that the valve moves and makes an operating noise.
OK:
Measurement Condition |
Specified Condition |
---|---|
Battery positive (+) with a 21 W bulb → Terminal 2 Battery negative (-) → Terminal 1 |
Valve moves and makes an operating noise |
If the result is not as specified, replace the solenoid valve.
4. INSPECT SHIFT SOLENOID VALVE S1
(a) Measure the resistance according to the value(s) in the table below.
Standard Resistance:
Tester Connection |
Condition |
Specified Condition |
---|---|---|
Shift solenoid valve S1 connector terminal - Shift solenoid valve S1 body |
20°C (68°F) |
11 to 15 Ω |
*a |
Component without harness connected (Shift Solenoid Valve S1) |
(b) Apply 12 V battery voltage to the shift solenoid valve and check that the valve moves and makes an operating noise.
OK:
Measurement Condition |
Specified Condition |
---|---|
|
Valve moves and makes an operating noise |
If the result is not as specified, replace the solenoid valve.
5. INSPECT SHIFT SOLENOID VALVE S2
(a) Measure the resistance according to the value(s) in the table below.
Standard Resistance:
Tester Connection |
Condition |
Specified Condition |
---|---|---|
Shift solenoid valve S2 connector terminal - Shift solenoid valve S2 body |
20°C (68°F) |
11 to 15 Ω |
*a |
Component without harness connected (Shift Solenoid Valve S2) |
(b) Apply 12 V battery voltage to the shift solenoid valve and check that the valve moves and makes an operating noise.
OK:
Measurement Condition |
Specified Condition |
---|---|
|
Valve moves and makes an operating noise |
If the result is not as specified, replace the solenoid valve.
Problem Symptoms Table
PROBLEM SYMPTOMS TABLE
HINT:
Use the table below to help determine the cause of problem symptoms. If multiple
suspected areas are listed, the potential causes of the symptoms are listed in order
of probability in the "Suspected Area" column of ...
Installation
INSTALLATION
PROCEDURE
1. INSTALL GENERATOR ASSEMBLY
(a) Install the generator bracket to the generator with the bolt.
Torque:
20 N·m {204 kgf·cm, 15 ft·lbf}
(b) Install the generator with the 2 bolts.
Torque:
43 N·m {438 kgf·cm, 32 ft·lbf}
(c ...